Responded to no heat complaint on 7-year-old Daikin furnace that was lighting but immediately extinguishing. Diagnosed failed flame sensor (reading 0.2 µA) which was not dirty but malfunctioning. Customer supplied replacement sensor which was installed, achieving proper microamp reading of 2.2 µA. System now heating normally after verifying all other components functioning properly.