Performed comprehensive furnace inspection on 11-year-old natural gas system. Identified and replaced multiple failing components including motor starter capacitor, flame sensor (reading under 2 microamps), ignitor, and inducer draft motor (running on high amps). CO levels in flue verified safe and system is now operational.