Responded to service call for Navien boiler system experiencing ignition failure. Diagnosed issue as inadequate gas pressure for high-fire operation on the current low-pressure LP system. Connected outdoor temperature sensor as temporary measure to reduce high-fire cycling. Customer will coordinate with LP provider to upgrade to required 2 PSI system. Return visit scheduled to install maxitrol regulator once gas company completes system upgrade.