Responded to no heat call for a system with a limit code and non-functioning blower. Identified that the new blower motor installed last week had a burned out low speed winding due to incorrect capacitor installation (10 mfd vs. required 5 mfd). Replaced with correct 5 mfd capacitor and rewired motor to utilize medium speed winding as a temporary solution until replacement motor arrives.