Tune-up: Furnace Tune-up: AC Performed complete furnace tune-up per heating checklist. Checked heat exchanger, igniter, inducer motor, blower motor, venting, safety limits, and gas pressure. Removed and cleaned flame sensor and burners. Performed combustion analysis. Inspected blower compartment, flushed out drain trap, drain lines and fittings. - Service Tech: Michael - Furnace: Lennox (2016) - Age of Equipment: 8yrs old - Filter: 16x25x4 - recently replaced by owner - Check Igniter Ohm: 52.0ohm - Checked Inducer Amps: rated: .65 actual: .25/.44A - Blower Amps: rated: 7.7 actual: 2.0/3.1A - Checked Gas Pressure: 1.6/3.4” - Temperature Rise: rated: 50-80 actual: 66F - CO in Exhaust: 16ppm - Humid