Found black hose was off pressure switch causing gas pressure to stay at 2.7 in low fire put on went to .69 where should had lots of codes for over heating started in February 2025 tested CO low fire originally tripped at 4000 ppm after adjusting went to 9ppm and 38 ppm in high fire to 14 ppm unit is now operating properly at this time.