Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed.

Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed. Responded to no-heat call on 3-year old HVAC system. Customer reported circulation motor issues with diagnostic flash codes 1+2. Upon inspection, determined that customer was not allowing for the system's required 90-second purge cycle before fan operation. Demonstrated proper operation to customer, verified multiple successful heating cycles, and confirmed system is functioning as designed with no repairs needed.