No cool due to a bad fuse. Last company took fuses and never got back. I put two new fuses (at disconnect box) and system works, but fan motor not spinning. Dual capacitor was reading low (30 and .86 on a 35/5 microfarad). Also, replaced dual capacitor. System works after that and is running and cooling the house as best as it can do. Contactor is making humming noise. System is 19 years old and on its last legs. Fan motor is very rusted and so the evaporator coil. Pressures are in ok shape, but rusted evaporator coil can lead to leaks. Also, system uses r22 (Freon) to cool the house. Due to the age and conditions of the system, Highly recommend to upgrade the AC system (furnace is newer -2021) and bring warranty, savings and efficiency back to the house. Set a lead to quote replacement for the AC only, for today. We should credit the money spent today (312,00) , if customer upgrade the ac system with us.