9800 Old Dogwood Rd.
Roswell, GA 30075
(770) 667-6937

Our Top Cities


Job Locations
for hiram, ga


Map of Hiram GA
Leeann W.

Leeann W.


Job Checkin

Tech was out for no cooling. Checked indoor and seen the following. No evap safety switch on drain line. Drain line needing to be cleared. Blower is needing to be cleaned. Condenser is needing a chemical cleaning. Cap has failed causing system not to come on. Also pressure where extremely high let customer know we would need to clean that way we can verify subcool and super heat. Before cleaning pressure were 144/443 sc 26 and sh 7.8 . After cleaning sc was still high adjusted charge. Now pressure are 137/369 sh 10/sc 14. Customer has signed up for home care we will be back to perform a maintenance in 5 months. At this system is operating.