Today I looked at the heat and cooling sides of the system. The although functional is out of tolerance to some degrees. Superheat 19 Subcool 10 TD 20 in cooling Concerns High inrush 152 Biogrowth on the face of evap coil and inside the system Recommend soft start and UV system.