Homeowner called us out due to hose bib not shutting off. The homeowner tried to shut off the hose bib at the handle and at the gate valve shut off inside, but that did not work . The water pressure of the home was also high with a reading of 75 psi. Replaced PRV and main shut off, as well as hose bib by carport. Tested and checked for leaks. The pressure to the home was set to 65 psi.