Came up to date to perform one system HVAC inspection. Po arrival customer stated that they had just recently bought the house and wanted everything inspected to ensure there were no issues with the system. Upon inspection of the system found that a return duct ran over the top of the unit, which is not code Due to there is no clearance for combustible material. Upon further inspection of the unit found that the outdoor condenser coil was very dirty, the system had a water float switch, the blower wheel was clean, the indoor coil was clean, the main power for the system was ran to a breaker that was connected to some bedrooms, an electrician will need to come out to give quote to add a breaker solely for the HVAC system, all functions and operations of the system were working properly. After speaking with customer, customer elected to go with Band-Aid option which included cleaning the outdoor coil, adding a water sensor, and re-running the return duct. After cleaning the coil and inst