We arrived back today. We came to fulfilled the estimate of a panel restoration, surge protector, and electrical grounding system. I first removed all of the existing breakers in the electrical panel and replaced them with new ones. Next time installed a search protector on the bottom of the panel. Last and that’s what grounding system was installed in the back of the house. Installed two 8’ ground rods on the backside of the house in front of those ground garage. We ran a number four ground wire all the way to the electrical panel where we installed a ground bar to mount it all. Inside the panel, all of the ground wires were removed from the neutral bar and installed on the new ground bar. I also installed a grounding jumper from the new ground bar over to the neutral bar. Last I separated, all double tapped neutrals on the neutral bar. It was great seeing you again, Karsten! Hope you and your family have a great year. If I can ever help you with anything else, please let me know.