Performed diagnostic on two units, upon arrival customer wasn’t onsite but explain unit 1 wasn’t working properly, stated outdoor fan wasn’t turning, checked tstat, cycled to ac mode, located air handler in ceiling, checked filter, very dirty, replaced customer provided filter, airflow, blower, recommend wet switch to prevent future water build up in secondary drain pan, , upon checking outdoor unit found compressor running but not fan, checked both capacitor, failed fan capacitor, recommend replacing, customer approved, installed new 7.5 capacitor, unit started up, checked contactor, amp draws, pressures, temp split,recommend chemical cleaning condenser coil, but customer doesn’t have access to water outside of building, made sure unit was draining properly, while outside noticed unit 2 wasn’t working , spoke with customer and he wanted unit 2 looked at as well, checked tstat, already in ac mode, upon checking air handler in ceiling found secondary drain pan full of water, recommend r