Upon arrival customer stated that ac unit was struggling to keep up inside the home on hotter parts of the day. After inspection of 9 year old furnace and ac unit, found that it takes a long time for metering device to equal out properly on both the suction and liquid line sides. Condenser coils were very dirty and clogged and have not been cleaned in a while, outdoor capacitor was bad and contactor was very pitted. Checked furnace in crawl space, blower wheel is dirty. (16x25x4) media filter was very dirty. Inside furnace was clean. Gave customer estimates to help system by cleaning outdoor coil, changing capacitor, changing contactor and adding a hard start to system, customer approved these repairs and signed up for 1 system homecare maintenance plan. Customer declined to add Uv light. Made all repairs for system and customer approved to have 1lbs r410a added to system to get subcool back to 10 degrees. Made all changes and tested system, advised customer that if he is still having