Job Locations
for commerce charter township, mi

Alex R.

Alex R. Job Checkin

Replaced bedroom hallway Horn/Strobe and are glass Rod for bedroom hallway pull station ***All systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Completed FACP REPLACEMENT and Completed full Systems Inspection /Completed Annual Fire Alarm/Fire Extinguisher/Emergency Light inspections for 2019 ***All systems Normal and Reset ***


Alex R.

Alex R. Job Checkin

Connected Fire Panel for Monitoring and tested system ***All systems normal and reset ***


Jeff D.

Jeff D. Job Checkin


Alex R.

Alex R. Job Checkin

Completed Annual Fire Extinguisher inspection for 2018


Dan S.

Dan S. Job Checkin

2-20 Ashley confirmed ATTN: Ashley Alman PH: (248) 624-7948 EMAIL: aalman@ustoremi.com . RE:      FIRE PROTECTION DEFICIENCIES NOTED FROM INSPECTION . Ashley, Thank you for choosing FIRE PROS, INC. as a service provider for your organization. We appreciate the opportunity to keep your facility fire safe and code compliant. During our recent inspection services, we found some items that require additional attention in order to be brought back up to code compliance. Please see the description below and the total cost for the service. . Emergency / Exit Lights Repair Exit / Emergency Lighting: During our recent Inspection Service, we found (44) fixtures that failed inspection due to to Bad Back-Up Batteries -which require replacement. We also found that (3) Emergency Light fixtures failed (2 due to bad Charging Boards and 1 is missing from its Mount) and (1) Exit Sign failed Inspection due to a Bad Charging Board requiring replacement. Below is a quick summary - repair > (44) Replace


Sean W.

Sean W. Job Checkin


Alex R.

Alex R. Job Checkin

Completed Annual Fire Alarm Inspection for 2017


Alex R.

Alex R. Job Checkin

Completed Annual Fire Alarm Inspection for 2017


Alex R.

Alex R. Job Checkin

Alarm Systems Emergency Service Call We have an open output circuit on #1 at Oak Valley that is sending a trouble signal. ***All systems are reset and normal at this time ***


Matthew B.

Matthew B. Job Checkin

Fire Sprinkler Systems: System Components (System Piping Obstruction Investigation & 2 System Check Valves) due for the NFPA 25 Code required 5-year Internal Inspection - perform Fire Sprinkler Systems: (4) Outdated System Pressure Gauges are due for replacement (every 5 years), as required by NFPA 25 Code - replace Fire Sprinkler Systems: Missing the necessary Head Wrench in the Spare Head Box - install Fire Sprinkler Systems: Missing (1) Control Valve and (1) Main Drain Sign on the Anti-Freeze System - replace


Matthew B.

Matthew B. Job Checkin

Fire Sprinkler Systems: System Components (System Piping Obstruction Investigation & 2 System Check Valves) due for the NFPA 25 Code required 5-year Internal Inspection - perform Fire Sprinkler Systems: (4) Outdated System Pressure Gauges are due for replacement (every 5 years), as required by NFPA 25 Code - replace Fire Sprinkler Systems: Missing the necessary Head Wrench in the Spare Head Box - install Fire Sprinkler Systems: Missing (1) Control Valve and (1) Main Drain Sign on the Anti-Freeze System - replace


Matthew B.

Matthew B. Job Checkin

Fire Sprinkler Systems: System Components (System Piping Obstruction Investigation & 2 System Check Valves) due for the NFPA 25 Code required 5-year Internal Inspection - perform Fire Sprinkler Systems: (4) Outdated System Pressure Gauges are due for replacement (every 5 years), as required by NFPA 25 Code - replace Fire Sprinkler Systems: Missing the necessary Head Wrench in the Spare Head Box - install Fire Sprinkler Systems: Missing (1) Control Valve and (1) Main Drain Sign on the Anti-Freeze System - replace


Matthew B.

Matthew B. Job Checkin

Replaced gauges that were out dated


Matthew B.

Matthew B. Job Checkin

Fire Sprinkler Systems: System Components (Piping x 2 & Alarm Check Valves x 4) have become due for the NFPA 25 Code required 5-year Internal Inspections - perform Fire Sprinkler Systems: Fire Department Connection (FDC) Check Valve in the Vocal Music Storage has become due for the NFPA 25 Code required 5-year Internal Inspection - perform Fire Sprinkler Systems: (9) Outdated System Pressure Gauges are due for replacement (every 5 years), as required by NFPA 25 Code - replace Fire Sprinkler Systems: Missing the necessary Head Wrench in the Spare Head Box - install