8/29/22 Confirmed by Rey for 8/30/22 / Sent email regarding inspection DH Sprinkler Inspection Deficiency: missing eight chrome esecu. viking Deficiency: 2 walk in coolers in back of building not protected. Large cooler will need 2 dry pendant heads and smaller cooler will need 1. Lift will be needed to reach supply piping above coolers. There is a “ main above that has 2” branch lines along it. Ceiling around 20 feet up. Deficiency: There is no evidence of five-year internal pipe obstruction investigation Deficiency: There is no evidence of five year internal check valve inspection for fire department connection also there is no evidence of five year Hydro test for fire department connection Deficiency: 2 walk in coolers in back of building not protected. Large cooler will need 2 dry pendant heads and smaller cooler will need 1. 12” Lift will be needed to reach supply piping above coolers. There is a “ main above that has 2” branch lines along it. Ceiling around 20 feet up. A li