6/14/23 Mike G will be going to this site as well he will be calling Alli, call Mike to coordinate. DH Sprinkler and Stand Pipe Inspection Annual Fire Sprinkler System Inspection (2 systems Located in Basement) Annual Standpipe Inspection (1) Deficiency: There is no evidence of five-year internal obstruction investigation of sprinkler systems 2- 4” Victaulic couplings 2- 3” Victaulic couplings Deficiency: Sprinkler systems are due for gauge change. 2- 300# air water 💦 gauges. Deficiency: Sprinkler head box will need one universal wrench and one 155° chrome pendant half-inch orifice quick response sprinkler head. 1 wrench 1- CPQR head. Deficiency: There is no evidence of five-year internal inspection of fire department connection check valve. Deficiency: There is no evidence of fire department connection hydrotest five year. Deficiency: Sprinkler system control valves will need signs and chain. 4- Control valve signs