2930 61st Street
Menomonie, WI 54751
715-283-4422

Our Top Cities


Job Locations
for eau claire, wi


Map of Eau Claire WI
Mike B.

Mike B.


Job Checkin

Responded to a commercial daycare facility for no heat complaint in classroom. Diagnosed blown fuse on air handler control board caused by electrical wiring shorting against copper refrigerant lines in the heat pump. Repaired by insulating and taping exposed wires to prevent future contact. Reset outdoor temperature lockout from disabled setting to 25°F to prevent heat pump operation in extreme cold conditions. System now operating normally.

Responded to a commercial daycare facility for no heat complaint in classroom. Diagnosed blown fuse on air handler control board caused by electrical wiring shorting against copper refrigerant lines in the heat pump. Repaired by insulating and taping exposed wires to prevent future contact. Reset outdoor temperature lockout from disabled setting to 25°F to prevent heat pump operation in extreme cold conditions. System now operating normally. Responded to a commercial daycare facility for no heat complaint in classroom. Diagnosed blown fuse on air handler control board caused by electrical wiring shorting against copper refrigerant lines in the heat pump. Repaired by insulating and taping exposed wires to prevent future contact. Reset outdoor temperature lockout from disabled setting to 25°F to prevent heat pump operation in extreme cold conditions. System now operating normally.