Responded to commercial furnace failure where unit was cycling off after 30 seconds of operation with blower running but no heat production. Diagnosed failed gas valve as root cause. Due to absence of service shutoff, temporarily disconnected gas to entire building to safely replace defective valve. Installed new gas valve with proper service shutoff, adjusted gas pressure to manufacturer specifications, and verified proper system operation through complete testing.