Ricardo V.


Job Checkin

No cool on the upstairs system. System is low on Freon and leaking at the suction line joint and in the evaporator coil, as well. Gave option for repair ( fix leaking, replace evaporator coil), but I don’t recommend any repair. System is 13 years old (furnace is new) , condenser fan motor is overamping (1.05 amps, and shouldn’t be higher than .95 amps, accordingly to the label), dual capacitor weak (reading 37 on a 40 microfarad) and compressor amperage is high (6.09 amps, and shouldn’t be higher than 9 amps ). Set a lead to quote upgrading the ac only, for Monday morning.