No cool on the upstairs system. System is low on Freon and leaking at the suction line joint and in the evaporator coil, as well. Gave option for repair ( fix leaking, replace evaporator coil), but I don’t recommend any repair. System is 13 years old (furnace is new) , condenser fan motor is overamping (1.05 amps, and shouldn’t be higher than .95 amps, accordingly to the label), dual capacitor weak (reading 37 on a 40 microfarad) and compressor amperage is high (6.09 amps, and shouldn’t be higher than 9 amps ). Set a lead to quote upgrading the ac only, for Monday morning.