Tech arrived to problem call for entire home. System is mixed in age, with indoor coils dirty being 7 years old and condenser being 10 years old. Furnace is roughly 6 years old. Customer had expressed that the outdoor fan motor was not always coming on and causing unit to shut off. Inspected system. Checked indoor unit. Customer filter was slightly dirty, customer will change on their schedule. Noticed liquid line getting extremely hot very quick. Indoor blower section is relatively clean and indoor capacitor is within specs. Customer has pan switch and condensate pump safeties. Secondary port has mastic putty and is shut. Checked outdoor unit. Condenser fan motor was not running and compressor was. Checked capacitor, capacitor was slightly out of tolerance but not enough to cause fan motor to stop (41/4.4 for 45/5). Was able to free fan motor briefly, and found motor overamping and extremely hot to the touch. Condenser coil is also very dirty. Brought recommendations to customer. Cu