Came out for no cool call on 2018 Goodman Heat Pump. Upon arrival customer let me know couple days ago turned static from 70 to 72 then that night got up to 79. Upon inspection found main issue is failed PSC blower motor. Verified 25Mfd capacitor good, and motor receiving proper 240v. Recommend replacing motor then verifying cooling operations after. Cleared out p trap, Verified draining. Found in line and emergency float switches but no wet switch. Made customer aware and recommended installing one for added flood protection. Also found vent for trap is not glued in, could potentially cause leak, recommend gluing in. Customer has washable 20x22 filter, recommended switching to regular filters or cleaning washable filters more often (once a month). System also has no UV protection, recommended APCO-X with Air Scrubber. Was not able to check outdoor unit amps or refrigerant charge due to no cooling. Verified weak outdoor capacitor as well, recommend proactively replacing. Also outdoor