Upon arrival customer stated that upstairs system was leaking on ceiling and that system was not cooling. After inspection of system found that unit had a clogged drain line and very restricted filter. There were parts of the suction line that weren’t taped and leaking water onto ceiling. Furnace is 2 years old ac unit is 6 years old. Blower wheel was clean, inside system was clean. Return plenum was very dirty. Checked outdoor system and condenser coils were very clogged, capacitor tested good with no issues, contactor tested good with no issues. Recommended cleaning drain line, removing water from drain pan, new supply and return plenum, cleaning outdoor condenser coils, and Uv light for system. Customer only wanted to have condenser coils cleaned and drain line, and removing water from drain pan. Made all repairs for system and unit is back up and cooling and draining properly. Customer wanted me to cleaned the other condenser unit as well, cleaned coils for system. When I went to t