2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for east grand rapids, mi


Map of East Grand Rapids MI
Gary B.

Gary B.


Job Checkin

Per Caleb they have electricians out right now and they accidently set off the kitchen system and need it recharged Suggested for RANGE-GUARD RG-4GM 4 GALLON MAIN HOOD / KITCHEN: System dumped when electrician went to run lines in the ceiling and moved the ceiling tile. Remote pull station conduit must have moved and dumped system.. There is MINIMAL room between ceiling tiles and ceiling, so could not get any pictures of conduit. Recommended to owners that they have Fire Pros return and run pull station conduit and wire below ceiling and have it mounted securely. Cannot investigate link line conduit in ceiling due to no ability to move ceiling tiles. Link line conduit is loose going above ceiling tiles. NEED TO QUOTE: (1) stick conduit (4) corner pulleys ((20’) cable (2) crimp (2) hours labor for (1) tech. (6) conduit clamps to firmly secure remote station link line conduit