2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for rochester hills, mi


Map of Rochester Hills MI
Terrence  J.

Terrence J.


Job Checkin

2/21/24 Confirmed by Chris for 2/26/24 at 8:00am DH / Sent email regarding inspection DH Sprinkler Inspection Annual Sprinkler Inspections (4) Wet (1) Dry Deficiency: Leak on 1” pipe and union in electrical room over by maintenance garage. Will need: 10’ of 1” pipe. (1) 1” union. Deficiency: Sprinkler system is due for gauge change. 1- sprinkler gauge Deficiency: Sprinkler system is due for five year internal obstruction investigation piping. 2- 4” victaulic couplings Deficiency: Sprinkler system is due for internal inspection five year fire department connection check valve. 2- 4” victaulic couplings Deficiency: Sprinkler system is due for five-year Hydro test of fire department connection Deficiency: System number two is due for five year internal obstruction investigation. 2- 4” victaulic couplings Deficiency: System number two is due for gauge change. 1- sprinkler gauge Deficiency: Dry pendant heads in cooler and freezer of administration building are to be removed an