Diagnosed heat pump and furnace synchronization issue where both systems were attempting to run simultaneously. Found heat pump providing insufficient temperature rise (only 15-20°F) before defaulting to furnace operation. Adjusted thermostat balance point from 20°F to 35°F to improve system coordination and recommended follow-up service with heat pump specialist for further evaluation.