Diagnosed no heat issue with Lennox zoned system, finding improper jumper wire configuration at zone control panel (RH to O instead of required RH to Rc). Corrected jumper placement, cut onboard jumpers, and reset thermostat from programming to non-programmable mode per customer preference. System testing confirmed proper operation with fan now functioning independently and with both heating and cooling modes.