Responded to no-heat call for 4-year-old LP furnace. Diagnosed low flame signal issue where furnace ignites but flames quickly extinguish. Gas pressure testing revealed adequate 11.5" WC pressure to valve before ignition that drops to near zero post-ignition. Suspected regulator failure with tank at 37% capacity. Advised homeowner to contact propane company for regulator replacement.