23 Year old Coleman Furnace/AC System not heating due to age. System has well exceeded its life expectancy and has multiple weak and outdated components. The igniter has failed, when testing voltage sent to the igniter I was getting fluctuating readings. 120-101-137-98 etc. The control board sends voltage to the igniter and the control board has a few hot spots “burned” areas on it. The inducer motor is over amping and has worn and noisy bearings, the blower motor is seeping oil at the main seal, the heat exchanger has several fractures, hot spots, and metal fatigue on it. The drain, gas line, and exhaust vent are not up to code. The cooling system is operating on R-22 refrigerant, this refrigerant is now obsolete and has gone through a Government Mandated Phase Out. After going over the age, condition, and lack of replacement parts for the equipment, I recommended updating the system. The homeowner requested we send out an install supervisor tomorrow afternoon and I set this appoint