9800 Old Dogwood Rd.
Roswell, GA 30075
(770) 667-6937

Our Top Cities


Job Locations
for atlanta, ga


Map of Atlanta GA
Terrance W.

Terrance W.


Job Checkin

Heat Pump Assessment & Recommendations The heat pump system is currently experiencing high startup amps (21 A vs. 17 A expected), indicating increased stress on the compressor. Contributing factors include:    •   Weak outdoor capacitor and a welded defrost board relay causing the fan to run continuously.    •   Dirty indoor blower wheel, evaporator coil, and filter, as well as a dirty outdoor coil, restricting airflow.    •   Unused upstairs zoning system, as the customer added a mini-split. Recommendations: 1. Remove the upstairs zoning board and dampers, and wire the system to the downstairs thermostat only. 2. Clean the evaporator and condenser coils and the blower wheel. 3. Replace the weak capacitor and install a hard start kit to reduce compressor strain. 4. Repair or replace the defrost board relay to ensure proper fan operation. Summary: These actions will restore airflow, reduce electrical strain, and extend the life and efficiency of the system. Given the condition of