-Hanger- From the Siemens sub-panel located by DL1 we wired in a new 120v 20 amp circuit for the hanger on the back side of the building. This circuit is attached to 5A on the panel board on a tandem 20/20 breaker. We used a 10g wire to help prevent a voltage drop from occurring. Inside the ha dig we used EMT conduit, straps, weather proof fittings and bell boxes to install (1) 20 amp weather rated GFCI and (1) 20 amp TRWR duplex outlet and (1) toggle switch and installed a new customer supplied fixture. After installing we tested the fixture and everything is working. -Guard Shack- From panel L1 we installed 1” EMT conduit up to 400’ to the exterior wall in the back corner to a disconnect. We used more conduit, weather rated fittings and a pvc tap box to get to the guard shack. We installed a #4 wire with a #10 ground to feed the guard shack to prevent a voltage drop. After installing we had a full load on the circuit and the drop was with the 5% range per NEC.