Today we came out for only system not heating rheem 3 ton heat pump split. Evaluated complete system found system low on refrigerant due to refrigerant leak. Performed electronic leak search found leaks in evaporator coil located in crawlspace. With coil leaking compressor has been compromised. Checked amp draws on all motors found condenser fan motor over amping Recommendations .9 data plate calls for .8 motor could fail at anytime. Client has no flood protection or emergency drain pan added flood note. Left band aid repair option and had install supervisor give options on updating