Henry H.

Henry H.


Job Checkin

Troubleshoot electrical issue. ISSUE: fridge had burning smell, vent hood shocks you when touched, LOCATION: kitchen FINDINGS: fridge outlet was backstabbed and 40 years old but not burnt or melted, internal wiring of fridge melted causing the smell and breaker to trip. Vent hood is leaking current to frame, and egc isn’t solid. Tested voltage from hot to neutral and got proper 124 volts. Tested voltage hot to ground and got 85 meaning the grounds are improperly bonded somewhere along the circuit RESOLUTION:replaced fridge outlet and installed dual function breaker for GFCI protection. Customer is getting new fridge. I gave estimates to Rewire circuit the vent hood is on, run a new vent hood circuit, and to redevice and remake all connections on vent hood circuit. Customer has other issues he needs to address first so I Left vent hood disconnected and capped off. Provide and install new fridge outlet, install dual function breaker to provide proper GFCI protection, install GFCI outl