Leaking PVC joint on Lennox 2018 90% furnace / @ptrap *** wasn’t glued looked to be dry fitted ** bird screen out flue vents outside ** dirty blower wheel and no flood protection on primary drainage for system , pan switch in drip pan was installed but wired incorrectly ** provided options for blower cleaning, flood protection on drainage and condensate pump replacement ** client signed up for homecare and repairs to be completed today ** Verified proper drainage after repairs and verified system operations afterwards… Existing water safety prior to my arrival / repair was wired to AC ( Y& C ) instead of be wired in series with R ( thermostat) ** First homecare visit will be summer / spring 2026 ** PREFERRED TECH ** As always thank you for choosing TE certified **