2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for dowagiac, mi


Map of Dowagiac MI
William S.

William S.


Job Checkin

Wet Building 29561 On riser: Remove and replace (5) outdated water gauges. NFPA 25 (13.2.7.2) Gauges shall be replaced every 5 years Wet Building 29561 On riser: Remove and replace the painted sprinkler head located in the riser room of building 29561. NFPA 25 (5.2.1.1.1) Any sprinkler that shows signs of any of the following shall be replaced; (6.) Paint other than that applied by the sprinkler manufacturer Wet Building 29561 On riser: Replenish the missing spare sprinkler heads in the spare headbox of buildings 29557, 29561, and 29555. NFPA 25 (5.4.1.5.4) The stock of spare sprinklers shall include all types and ratings installed and shall be as follows; Facilities having under 300 sprinklers – minimum of 6 spare sprinklers Wet Building On riser: Add the missing supervision to the control valves of all five systems. This will prevent tampering with. NFPA 25 (13.3.1.3) Each normally open valve shall be secured utilizing a seal or a lock or shall be electrically super