2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for orion township, mi


Map of Orion Township MI
Terrence  J.

Terrence J.


Job Checkin

Sprinkler Inspection Annual Fire Sprinkler Inspection (1 Wet System) 5yr Internal Due: 2025 FDC Hydro Due: 2025 Deficiency: Pendants in upright position in basement. Replace with uprights (2) 1/2” 155 QR brass uprights Deficiency: Out dated dry heads are due for testing. From 2020 write up: 4- SIDEWALL 155 degree quick response heads 8” long 2- SIDEWALL 155 degree quick response heads 20” long 4- PENDANT 155 degree quick response heads length unknown. Above walk in on first floor has drywall enclosing it above the drop ceiling. Need to cut access to reach. Also need to cut access hole in women’s restroom to reach back sidewall head. ALL DRY BARREL HEADS NEED A “T” FITTING AND PLUG TO BE PROPERLY INSTALLED. All are piped in with 90 degree elbows. 3 sidewalls in basement walk ins all 8” long 1 sidewall at front door 8” long 2 sidewalls in back for outside dining area. 20” long 4 pendant heads for first floor walk in. also where the four pending heads are there is no access