Gary B.

Gary B.


Job Checkin

Deficiency for Pyro Chem PCL-300 3 gallon Main Hood: Number of Systems failed : 1 NO Audio/Visual notification Electric to convection oven does NOT shut down when system is activated. Lori said she will have electrician fix. 2H nozzle needs to be dropped a total of 36” and have swivel nozzle added -36” pipe -36” chrome sleeve -swivel nozzle Need to remove and plug (2) appliance drops no longer needed Need to lower Class K and add Class K signage Semi-Annual Kitchen Hood Fire Suppression System Inspection (PCL-460?) Kitchen Suppression Inspection