2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for flat rock, mi


Map of Flat Rock MI
Jim S.

Jim S.


Job Checkin

10/15 Scheduled with Paul via email Unconfirmed km Portable Extinguishers and Kitchen Suppression Inspection Annual Fire Extinguisher Inspection (4 FE?) Semi-Annual Kitchen Hood Fire Suppression System Inspection (Ansul 9gl?) Deficiency: Number of Systems failed : 1 Deficiency: Electric (fuel source on oven and non fuel source on pressure fryers and deep fryers under main hood do not de energize upon fire system actuation. Deficiency: Firing pin and cartridge in universal control head is out of hydro date.