Emergency Exit Lighting Deficiency: (2) Inoperable Exit Lights (Bad Charging Boards/Transformers) During your most recent Fire Protection Inspection, our technicians noted that one or more of your Emergency Exit Lights are inoperable per: NFPA 101: 7.10.1.2 All exit signs must be illuminated by a reliable light source and must be legible in both normal and emergency exit lighting modes. Emergency Exit Lights are crucial to guiding people out of a building or structure in the event of power loss or fire. Scissor Linkage Deficiency: (6) Stainless Steel Link Holders Needed (Both Fryer Hoods) During the inspection of the fire suppression system, the technician noted that the aluminum link holders no longer meet the requirements of ANSI/NFPA/UL300 and the manufacturer and will need to be replaced with stainless steel link holders. 10.2.3* Automatic Fire-Extinguishing systems SHALL comply with ANSI/UL300 or other equivalent standards and shall be installed in accordance with the requiremen
Kitchen Suppression, Emergency / Exit Lights, and Portable Extinguishers Inspection