Sprinkler Inspection FP Semi Annual Deficiency: Missing sprinkler wrench 5.4.1.6* A special sprinkler wrench shall be provided and kept in the cabinet to be used in the removal and installation of sprinklers No spare head wrench in head box. To fix we need: 1- tyco double sided head wrench
Sprinkler Repair Air Leak and Full Flow Trip Test (Dry System) At a recent inspection, it was noted that there is no record of air leak testing or a full flow trip test having been performed on your dry sprinkler system in the last three years. Per NFPA 25 13.4.4.2.2.2*Every 3 years and whenever the system is altered, the dry pipe valve shall be trip tested with the control valve fully open and the quick-opening device, if provided, in service. And per NFPA 25 13.4.4.2.9Dry pipe systems shall be tested once every 3 years for air leakage, using one of the following test methods: (1) A pressure test at 40 psi (3.2 bar) shall be performed for 2 hours. (a) The system shall be permitted to lose up to 3 psi (0.2 bar) during the duration of the test. (b) Air leaks shall be addressed if the system loses more than 3 psi (0.2 bar) during this test.Nelbud proposes to perform the required air leak testing and full flow trip test of your dry fire sprinkler system. Dry Sprinkler Head Sampling
Kitchen Exhaust Cleaning Cleaning KEC Quarterly - Main (Flat Top;Oven;Stove)
Sprinkler Head Replacement Needed: During the recent inspection of the sprinkler system, the technician noted that multiple sprinkler heads were found to be corroded and need to be replaced. 5.2.1.1.1* Any sprinkler that shows signs of any of the following shall be replaced: (1) Leakage (2) Corrosion detrimental to sprinkler performance (3) Physical damage (4) Loss of fluid in the glass bulb heat-responsive element (5) Loading detrimental to sprinkler performance (6) Paint other than that applied by the sprinkler manufacturer The proposal below is all-inclusive and includes all parts and labor. You can accept this proposal electronically or contact me directly.
Dry system tripped. Anti-drain the system and reset the dry valve and left in service. Got a material list for pipe needed to make repairs for the leaks in the outside dock area.
Sprinkler Inspection Dry South end of building: FP Annual Dry Wet Basement Outside Wall Tire Shop: FP Annual Wet Dry North Specialized Equipment: FP Annual Dry Wet Basement Outside Wall Tire Shop: FP Annual Wet Wet Just outside Fire Truck Fleet Room: FP Annual Wet
Sprinkler Inspection FP Annual Deficiency: Five year due Suggested for Wet Mechanical room: Gauges on system need replaced per five years
Sprinkler Inspection Wet Front of truck bay: FP Annual