11/29/22 Emailed regarding inspection DH 11/14/22MV Called Costco and spoke MOD, Gm is calling back when they can get us in Sprinkler Inspection Semi-Annual Sprinkler Inspection (Annual done 2 times per yr) (4 Wet and 1 Dry Sprinkler Systems) Deficiency: There is no evidence of five-year internal obstruction investigation of dry sprinkler system. Deficiency: There is no evidence of five-year internal inspection of dry alarm valve. Deficiency: Sprinkler gauges are due for a change. Deficiency: There is no evidence of five-year internal inspection on dry sprinkler risers. Deficiency: Which sprinkler systems will need gauge chains a total of eight. Deficiency: There is no evidence of five-year internal inspection of fire department connection. Deficiency: There is no evidence of five year Hydro test on fire department connection. The On the outside is a STORTZ connection.