Terrence  J.

Terrence J.


Job Checkin

ANNUAL FIRE SPRINKLER WET SYSTEM TEST AND INSPECTION.  ANNUAL FIRE SPRINKLER 6" WALL PIV TEST AND INSPECTION.  ANNUAL FIRE EXTINGUISHER TEST AND INSPECTION Sprinkler Inspection Annual Fire Sprinkler System Inspection - S/W Warehouse Deficiency: There is no evidence of five-year internal inspection check valve fire department connection and sprinkler alarm valve. Deficiency: There is no evidence of five-year internal obstruction investigation sprinkler system Deficiency: There is no evidence of five-year Hydro test fire department connection Deficiency: Sprinkler system is due for gauge change.