Job Checkin

5/22/23 Confirmed with Frank D. for 5/23/23 at 11:30amish DH / Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler System Inspection Deficiency: Sprinkler system is due for gauge change. 1- gauge Deficiency: Fire department connection check valve due for five-year internal inspection. 2- Victaulic couplings 4” Deficiency: Sprinkler system is due for five year internal obstruction investigation. 2 - 4” Victaulic couplings Deficiency: Sprinkler system fire department connection due for five year Hydro test. Deficiency: The sprinkler system has three rollup doors next to riser that have no protection under the doors these doors will have to be protected so that they are covered under NFPA fire code. it is possible that the city of Lavonia will require a permit for this work we must clear with the city how they will want us to proceed and then we can measure and fabricate piping according to specs that they lay out.