2710 Northridge Dr. Suite #F
Grand Rapids, MI 49544
1-800-968-2871

Our Top Cities


Job Locations
for plymouth, mi


Map of Plymouth MI
Terrence  J.

Terrence J.


Job Checkin

4/17/23 Confirmed via email with Jeff G. for 4/27/23 at 9:00am DH / Sent email regarding Inspection DH Sprinkler Inspection Ann Wet Sprink, Ann Dry Sprink Deficiency: Canopy dry system is due for gauge change parts needed 2 sprinkler gauges Deficiency: There is no evidence of five year internal investigation check valve dry system canopy. Deficiency: There is no evidence of five-year obstruction investigation of canopy system piping. 2-4”Victaulic couplings. Deficiency: Sprinkler system in main riser room wet Due for a five-year internal obstruction investigation Deficiency: Sprinkler system and main riser room dry due for five year internal inspection obstruction investigation. We will need 4- 4 inch Victaulic couplings Deficiency: Wet sprinkler system in main riser room sprinkler heads that are quick response are due for testing. 4-Horizontal side walls chrome will be needed to perform testing Suggested: Fire department connection due for Hydro test but check valve is in accessible