8/7/23 Confirmed with Terry MGR for 8/10/23 in the afternoon Dh / Sent email regarding inspection DH Sprinkler Inspection Annual Fire Sprinkler System Inspection (1 wet system) Deficiency for 4” wet riser in riser closet next to front entrance, ITV in kitchen by rear exit: Control valves are not identified or supervised. (2) control valve signs Sign chain (1) break away lock Deficiency for 4” wet riser in riser closet next to front entrance, ITV in kitchen by rear exit: Main drain is not identified. (1) main drain sign Sign chain Deficiency for 4” wet riser in riser closet next to front entrance, ITV in kitchen by rear exit: Missing spare head box, spare heads, and spare head wrench. (1) 6 count head box (3) 1/2” 155 QR brass uprights (1) head wrench 12” uni strut (1) 2” uni strut clamp (2) 3/8” washers, uni strut nuts, and bolts Mount to main drain pipe Deficiency for 4” wet riser in riser closet next to front entrance, ITV in kitchen by rear exit: FDC check valve is due for a 5 yea