3/20/23 Backflow has been repaired DH 1/16/23 Backflow is still broken will need to repair before inspection DH Annual Fire Sprinkler Inspection (1 Wet System) 5-Year Internal Due: FDC Hydro Due: Deficiency: Pipe burst in between first and second valve. Released main drain and closed first valve. Inoperable Deficiency: Backflow replacement for frozen backflow . See pictures for all info . Deficiency: Found Lower Riser Control Valve closed and no pressure on the Fire Riser. Inoperable Deficiency: The backflow on the sprinkler system has been damaged in a freeze it has not been replaced at all therefore system is totally in operable at this time.