Tech found coil completely frozen on circuit 2. Circuit 1 has been down since September. Tech thawed coil and leak searched system. No leaks present. Tech found normal head pressure at 320 with 80 degree outdoor temp, low suction and high superheat. This indicates a restriction. Tech found orifices freezing directly after metering device and tech recommends replacing coil. Tech also found a cracked belt and recommends replacing it as well. Tech recommended looking at comparing repair price to unit price. Field supervisor notified