Matthew L.

Matthew L.


Job Checkin

Tech performed ESA maintenance on Goodman split system. Tech found indoor coil leaking R22 refrigerant. See video. Tech also found compressor megohm tested in the caution range. See picture. Office will follow up on mandatory. After cleaning system, tech checked R22 pressures. Total system charge is about 13.5 lbs of R22. Tech estimates system is 3 to 5 lbs low. Quoted 5 lbs of R22 and leak freeze. Need to reach back out on follow up for Field Supervisor.