Tech found compressor not starting in R22 outdoor unit due to failed 40/5uf 370VAC dual run capacitor. Tech replaced capacitor for testing purposes and found system back cooling. R22 pressures are low, but outdoor temperature is cool this morning. Tech called for heating and found middle heat strip cutting off on thermal overload snap disc. All three heat strips do run, but blower wheel may need to be cleaned and increase PSC blower speed to increase airflow and prevent heat strip from cycling on and off at snap disc limit. 7.5uf blower capacitor is reading very weak at 3.58uf. Outdoor coil looks corroded from possible dog urine. Tech confirmed indoor coil is leaking. Detector indicated hit on high sensitivity but not medium. Tech recommends thoroughly cleaning system before adding R22. Recommended ESA. Customer declined all repairs due to price. No interest in repairs or replacement at this time.